FHEO/UFAS (Building Exterior) |
This inspectable item can have the following deficiencies: |
Main Entrance Less Than 32″ Wide |
Obstructed or Missing Accessibility Route |
Main Entrance Less Than 32″ Wide (FHEO/UFAS—Building Exterior) |
Deficiency: Verify that the main entrance
for each building inspected is at least 32″ wide, measured from
between the face of the door and the opposite door stop. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The distance
between the face of the door and the opposite doorstop is not
32” wide. |
Obstructed or Missing Accessibility Route (FHEO/UFAS—Building
Exterior) |
Deficiency: Verify that there is an
accessible route to and from the main ground floor entrance for
every building inspected. Accessible routes include level
surface to the door, ramps, etc. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: There is not
an accessible route. |
Fire Escapes (Building Exterior) |
All buildings must have acceptable fire exits. This includes
both stairway access doors and external exits. These can include
external fire escapes, fire towers, operable windows on the
lower floors with easy access to the ground or a back door
opening onto a porch with a stairway leading to the ground. |
This inspectable item can have the following deficiencies: |
Blocked Egress/Ladders |
Visibly Missing Components |
Blocked Egress/Ladders (Fire Escapes—Building Exterior) |
Deficiency: Any part of the fire escape,
including ladders, is blocked, limiting or restricting people
from exiting. |
Note: This includes fire escapes, fire towers, and windows on
the ground floor that would be used in an emergency. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: Stored items
or other barriers restrict or block people from exiting. |
Visibly Missing Components (Fire Escapes—Building Exterior) |
Deficiency: You see that any of the
components that affect the function of the fire escape are
missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see that
any of the functional components that affect the function of the
fire escape, for example, 1 section of a ladder or a railing, is
missing. |
Foundations (Building Exterior) |
Lowest level structural wall or floor responsible for
transferring the building's load to the appropriate footings and
soil. Materials may include concrete, stone, masonry and wood. |
This inspectable item can have the following deficiencies: |
Cracks/Gaps |
Spalling/Exposed Rebar |
Cracks/Gaps (Foundations—Building Exterior) |
Deficiency: You see a split in the exterior
of the lowest structural wall. |
Note: Cracks that show evidence of water penetration should be
evaluated here. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see
cracks more than 1/8 inch wide by 1/8 inch deep by 6 inches
long. |
-OR- |
You see large pieces, for example, many bricks, that are
separated or missing from the wall or floor. |
- Level 3: You see large
cracks or gaps more than 3/8 inch wide by 3/8 inch deep by 6
inches long, a possible sign of a serious structural problem. |
-OR- |
You see cracks that are the full depth of the wall, providing
opportunity for water penetration. |
-OR- |
You see sections of the wall or floor that are broken apart. |
Comment: |
- Level 3: If you have
any doubt about the severity of the problem, request an
inspection by a structural engineer. |
Spalling/Exposed Rebar (Foundations—Building Exterior) |
Deficiency: A concrete or masonry wall is
flaking, chipping, or crumbling, possibly exposing underlying
reinforcing material (rebar). |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see
obvious, large spalled area(s) affecting 10% to 50% of any
foundation wall. |
- Level 3: You see
obvious, significant spalled area(s) affecting more than 50% of
any foundation wall. |
-OR- |
You see spalling that exposes any reinforcing material, such as
rebar or other. |
Comment: |
- Level 3: If you have
any doubt about the severity of the problem, request an
inspection by a structural engineer. |
Lighting (Building Exterior) |
System to provide illumination of building exteriors and
surrounding grounds. Includes fixtures, lamps, stanchions,
poles, supports, and electrical supply that are associated with
the building itself. |
Broken Fixtures/Bulbs (Lighting—Building Exterior) |
Deficiency: Includes broken fixtures and bulbs. This deficiency
covers all or part of the lighting associated with the building,
including lighting attached to the building used to light the
site. If you see lighting that is not directly attached to a
specific building, assign it to the nearest building. |
Note: If a damaged fixture or bulb presents a safety hazard,
rate it as Level 3, and record it manually as a health and
safety concern. This includes broken fixtures and bulbs that
could fall on pedestrians or could lead to electrocution. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: 20% to 50% of
the lighting fixtures and bulbs surveyed are broken or missing,
but this does not constitute an obvious safety hazard. |
- Level 3: More than 50%
of the lighting fixtures and bulbs surveyed are broken or
missing. |
-OR- |
The condition constitutes an obvious safety hazard. |
Comment: |
- Level 3: If the
condition is a health and safety concern, you must record it
manually under “Electrical Hazards (Health and Safety).” |
Roofs (Building Exterior) |
Roof system consists of the structural deck, weathering surface,
flashing, parapet, and drainage system. They may be flat or
pitched. |
This inspectable item can have the following deficiencies: |
Damaged/Clogged Drains |
Damaged Soffits/Fascia |
Damaged Vents |
Damaged/Torn Membrane/Missing Ballast |
Missing/Damaged Components from Downspout/Gutter |
Missing/Damaged Shingles |
Ponding (Roofs) |
Damaged/Clogged Drains (Roofs—Building Exterior) |
Deficiency: The drainage system does not
effectively remove water. Generally, this deficiency applies to
flat roofs. |
Note: |
1. This does not include gutters and downspouts. For these, see
“Missing/ Damaged Components from Downspout/Gutter
(Roofs—Building Exterior).” |
2. If there has been measurable precipitation (1/10 inch or
more) during the previous 48 hours, consider the impact on the
extent of the ponding. Determine that ponding has occurred only
when there is clear evidence of a persistent or long-standing
problem. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see
debris around or in a drain, but no evidence of ponding. |
-OR- |
The drain is damaged or partially clogged with debris, but the
drain system still functions and you see no evidence of ponding. |
- Level 3: The drain is
so damaged or clogged with debris that the drain no longer
functions, as shown by ponding. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, an inspection by
a roofing specialist is recommended. |
Damaged Soffits/Fascia/Soffit Vents (Roofs—Building Exterior) |
Deficiency: You see damage to soffit,
fascia, soffit vents, or associated components that may provide
opportunity for water penetration or other damage from natural
elements. |
Level of Deficiency: |
- Level 1: You see
damage to soffits, fascia or soffit vents, but no obvious
opportunities for water penetration. |
- Level 2: N/A |
- Level 3: Soffits,
fascia or soffit vents that should be there are missing or so
damaged that water penetration is visibly possible. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, an inspection by
a roofing specialist is recommended. |
Damaged Vents (Roofs—Building Exterior) |
Deficiency: Damaged vents on or extending
through the roof surface or components are damaged or missing.
Vents include ridge vents, gable vents, plumbing vents, gas
vents, and others. |
Note: This does not include exhaust fans on the roof or soffit
vents: |
- Exhaust fans are covered under “Roof Exhaust System (Building
Systems).” |
- Soffit vents are covered under “Damaged Soffits/Fascia/Soffit
Vents (Roofs—Building Exterior).” |
Level of Deficiency: |
- Level 1: The vents are
visibly damaged, but do not present an obvious risk to promote
further roof damage. |
- Level 2: N/A |
- Level 3: Vents are
missing or so visibly damaged that further roof damage is
possible. |
Damaged/Torn Membrane/Missing Ballast (Roofs—Building Exterior) |
Deficiency: In the membrane or flashing, you
see damage that is a rip or tear, including punctures, holes,
cracks, blistering, and separated seams. PVC, rubber, bitumen,
and similar materials are all subject to tears and punctures. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: Ballast has
shifted and no longer functions as it should. |
- Level 3: You see signs
of damage, as defined above, to the membrane that may result in
water penetration. |
Comment: |
- Level 3: If the
condition warrants further inspection, inspection by a roofing
specialist is recommended. |
Missing/Damaged Components from Downspout/Gutter (Roofs—Building
Exterior) |
Deficiency: You see that components of the
drainage system, including gutters, leaders, downspouts,
splashblocks, and drain openings, are missing or damaged. |
Note: This does not include clogged drains. For clogged drains,
see “Damaged/Clogged Drains (Roofs—Building Exterior).” |
Level of Deficiency: |
- Level 1: Splashblocks
are missing or damaged. |
- Level 2: You see that
drainage system components are missing or damaged, but there is
no visible damage to the roof, structure, exterior wall surface,
or interior. |
- Level 3: You see that
drainage system components are missing or damaged, causing
visible damage to the roof, structure, exterior wall surface, or
interior. |
Missing/Damaged Shingles (Roofs—Building Exterior) |
Deficiency: Shingles are missing or damaged,
including cracking, warping, cupping, and other deterioration. |
Note: A square is 100 square feet. |
Level of Deficiency: |
- Level 1: Up to 1
square of surface material or shingles is missing or damaged
from roof areas you survey. |
- Level 2: One to 2
squares of surface material or shingles are missing or damaged
from surveyed roof areas. |
- Level 3: More than 2
squares of shingles are missing or damaged from surveyed roofing
areas. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, an inspection by
a roofing specialist is recommended. |
Ponding (Roofs—Building Exterior) |
Deficiency: You see evidence of areas of
standing water, such as roof depression, mold ring, or
effervescence water ring. |
Note: If there has been measurable precipitation (1/10 inch or
more) during the previous 48 hours, consider the impact on the
extent of the ponding. Determine that ponding has occurred only
when there is clear evidence of a persistent or long-standing
problem. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
evidence of standing water on the roof, causing potential or
visible damage to roof surface or underlying materials. |
Comment: |
- Level 3: If you have
any doubt of the severity of the condition, an inspection by a
roofing specialist is recommended. |
Walls (Building Exterior) |
The exterior enclosure of the building or structure. Materials
for construction include concrete, masonry block, brick, stone,
wood, glass block. Surface finish materials include metal, wood,
vinyl, stucco. |
Note: This does not include foundation walls. |
This inspectable item can have the following deficiencies: |
Cracks/Gaps |
Damaged Chimneys |
Missing/Damaged Caulking/Mortar |
Missing Pieces/Holes/Spalling |
Stained/Peeling/Needs Paint |
Cracks/Gaps (Walls—Building Exterior) |
Deficiency: You see a split, separation, or
gap in the exterior walls. |
Note: If you see both cracks/gaps and missing
pieces/holes/spalling, do not record both. If you see both
deficiencies, record only 1 of the 2. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see a
crack or gap that is more than 1/8 inch wide by 1/8 inch deep by
6 inches long. |
-OR- |
You see pieces, for example, many bricks, that are separated
from the wall. |
- Level 3: You see a
large crack or gap that is more than 3/8 inch wide or deep and 6
inches long, possibly a sign of a serious structural problem. |
-OR- |
You see a crack or gap that is the full depth of the wall,
providing opportunity for water penetration. |
-OR- |
You see sections of the wall that are broken apart. |
Comment: |
- Level 3: If you have
any doubt of the severity of the condition, request an
inspection by a structural engineer. |
Damaged Chimneys (Walls—Building Exterior) |
Deficiency: The chimney, including the part
that extends above the roofline, has separated from the wall or
has cracks, spalling, missing pieces or broken sections
(including chimney caps). |
Level of Deficiency: |
- Level 1: The chimney
cap is either visibly loose or damaged. |
- Level 2: The surface
of the chimney shows surface damage on more than 1 piece of
wall, for example, a few bricks or a section of siding. |
-OR- |
The surface of the chimney has holes that affect an area larger
than 4 inches by 4 inches. |
- Level 3: Part or all
of the chimney has visibly separated from the adjacent wall. |
-OR- |
There are cracked or fallen pieces or sections. |
-OR- |
There is a risk that falling pieces could create a safety
hazard. |
Comment: |
- Level 3: If the
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Missing/Damaged Caulking/Mortar (Walls—Building Exterior) |
Deficiency: Caulking designed to resist
weather or mortar is missing or deteriorated. |
Note: This does not include caulking relative to doors and
windows; they are covered in other areas. Address all other
caulking here. |
Level of Deficiency: |
- Level 1: Mortar is
missing around a single masonry unit. |
-OR- |
Deteriorated caulk is confined to less than 12 inches. |
- Level 2: Mortar is
missing around more than 1 contiguous masonry unit. |
-OR- |
You see deteriorated caulking in an area longer than 12 inches. |
- Level 3: N/A |
Missing Pieces/Holes/Spalling (Walls—Building Exterior) |
Deficiency: You see deterioration of the
exterior wall surface, including missing pieces, holes, or
spalling. This may also be attributed to: |
—Materials that are rotting. |
-OR- |
—A concrete, stucco, or masonry wall that is flaking, chipping
or crumbling. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see that
there is a missing piece, for example, a single brick or section
of siding, or a hole larger than 1/2 inch in diameter. |
-OR- |
You see deterioration that affects an area up to 8 1/2 inches by
11 inches |
- Level 3: You see
deterioration that exposes any reinforcing material (rebar). |
-OR- |
You see more than 1 missing piece, for example, a few bricks or
a section of siding, or holes that affect an area larger than 8
1/2 inches by 11 inches. |
-OR- |
You see a hole of any size that completely penetrates the
exterior wall. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, request an
inspection by a structural engineer. |
Stained/Peeling/Needs Paint (Walls—Building Exterior) |
Deficiency: Paint is cracking, flaking, or
otherwise deteriorated. Water damage or related problems have
stained the paint. |
Note: This does not include walls that are not intended to have
paint, such as most brick walls, etc. |
Level of Deficiency: |
- Level 1: You observe
that less than 50% of a single building exterior wall is
affected. |
- Level 2: You observe
that more than 50% of a single building exterior wall is
affected. |
- Level 3: N/A |