Inspectable Area: Units and Common Areas
|
Deficiency
Notes |
|
Chutes Damaged/Missing Components (Common Areas) |
Deficiency: The structure that directs
garbage into the appropriate storage container is missing or
damaged. This includes the chute, chute door, and other
components. |
Note: Do not evaluate the door that leads to the trash room. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: Garbage has
backed up into chutes, because the collection structure is
missing or broken. Compactors or components, chute, chute door,
and other components, have failed. |
- Level 3: N/A |
|
|
|
|
The main issue we find cited
here is trash chutes doors that do not close and latch automatically as
they should.
Old trash chute doors can become a nuisance, and they so frequently fail
to work that it becomes a very routine thing, and gets forgotten.
It's a 1 to 2 point deduction if this is cited as Level 3 |
|
|
It is "fair game" for your
inspector to ask you to operate the trash compactor if you have one.
If it does not work, that is a deficiency as well. |
|
Be sure to review all Unit/Common Area Inspectable Items, and
remember that we have covered Doors, Electrical, many HVAC and Hot Water
Heater, and Lighting issues in other sections like Electrical and
Systems/Mechanical.
For example: there is one Unit/CA HVAC issue that does not exist at the
Bldg Systems level, it can only be cited as a Unit/CA issue - see below: |
|
|
Convection/Radiant Heat System Covers Missing/Damaged
(HVAC—Unit) |
Deficiency: A cover on the
convection/radiant heat system is missing or damaged, which
could cause a burn or related injury. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: At least 1
cover is missing or substantially damaged, allowing contact with
heating/surface elements or associated fans. |
Comment: |
- Level 3: When the
system is operational during an inspection and you see a Level 3
deficiency, a real-time hazard exists, you must record it
manually under “Hazards (Health and Safety).” |
|
|
|
|
This missing cover is Level 3.
The scoring value is
surprisingly high compared to some other defects - but that's not the
worst of this . . .
This is also often cited as a Sharp
Edges hazard for an additional point deduction, so that a missing or
damaged baseboard heater cover can end up costing MORE than a full point
in deductions. |
|
Plumbing—Clogged Drains (Bathroom—Unit) |
Deficiency: Water does not drain adequately
in the shower, tub, or basin (sink). |
Level of Deficiency: |
- Level 1: Water does not
drain freely, but the fixtures can be used. |
- Level 2: N/A |
- Level 3: The fixtures
are not usable, because the drain is completely clogged or shows
extensive deterioration. |
|
|
|
|
We'll talk about the missing
stopper later - let's deal with the clogged drain first.
A slow drain is Level 1.
A stopped drain is Level 3.
How slowly does it have to drain, in order to call it Level 3?
This is pretty much left up to inspector judgment.
|
|
Plumbing—Leaking Faucet/Pipes (Bathroom—Unit) |
Deficiency: You see that a basin, shower,
water closet, tub faucet, or associated pipes are leaking water. |
Level of Deficiency: |
- Level 1: You see a leak
or drip that is contained by the basin, and the faucet or pipe
can be used. |
- Level 2: N/A |
- Level 3: You see a
steady leak that is adversely affecting the area around it. |
-OR- |
The faucet or pipe cannot be used. |
|
"Contained by the basin:" the
water does not go out of the sink.
"Cannot be used" means without creating a problem... like
"adversely affecting the area around it." |
|
|
This drain works much better -
the water goes right down the drain... right into this BUCKET.
If the water goes down the drain, it is a Level 1 leak...
UNLESS it then goes somewhere else, like on to the floor or into this
bucket!
Now it is Level 3 |
|
Lavatory Sink—Damaged/Missing (Bathroom—Unit) |
Deficiency: A basin (sink) is missing or
shows signs of deterioration or distress. |
Note: If you see the stopper near the sink area, do not record
it as a deficiency. |
Level of Deficiency: |
- Level 1: The sink can
be used, but you see either of these: |
—There are cracks or extensive discoloration in more than 50% of
the basin; |
-OR- |
- A stopper is missing. |
- Level 2: N/A |
- Level 3: The sink
cannot be used, because the sink or associated hardware is
missing or has failed. |
|
|
|
|
The missing stopper is
Lavatory/Sink Damaged/Missing, Level 1
Until recently it was held that a rubber stopper was a reasonable
substitute for the original mechanical stopper, and that no defect
should be cited if a rubber stopper was present.
More recent instructions from REAC say that this is still a defect if
the plunger that operated the mechanical stopper is still present.
In other words: some inspectors will still cite this as Level 1 if the
plunger is there or even if the little hole has not been filled.
The damage to the sink basin itself in this photo is not enough to cite. |
|
Water Closet/Toilet—Damaged/Clogged/Missing (Bathroom—Unit) |
Deficiency: A water closet/toilet is damaged
or missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: Fixture
elements, seat, flush handle, cover etc., are missing or
damaged. |
-OR- |
The toilet seat is cracked, or the hinge is broken. |
- Level 3: The bowl is
fractured or broken and cannot retain water. |
-OR- |
The water closet/toilet is missing. |
-OR- |
There is a hazardous condition. |
-OR- |
The water closet/toilet cannot be flushed, because of
obstruction or another defect. |
|
|
|
|
Even though this is a resident
installed toilet seat, the tear or crack makes it a
Level 2 defect.
A loose seat would be Level 2.
Any missing or damaged part that still allows the toilet to be safely
usable is Level 2.
If inoperable or unsafe, the toilet is Level 3.
Some say that a "running toilet" (leak at the fill valve) is a Level 2
Toilet defect. Others say it is a Level 1 Plumbing Leak.
The toilet defect is the higher scoring of the two, and the more common
citation. |
|
Bathroom Cabinets—Damaged/Missing (Bathroom—Unit) |
Deficiency: You see damaged or missing
cabinets, vanity tops, drawers, shelves, doors, medicine
cabinets, or vanities. |
Level of Deficiency: |
- Level 1: You see
damaged or missing cabinets, vanity tops, drawers, shelves,
doors, medicine cabinets or vanities that are not functioning as
they should for storage or their intended purpose. |
- Level 2: N/A |
- Level 3: N/A |
Plumbing—Leaking Faucet/Pipes (Bathroom—Unit) |
Deficiency: You see that a basin, shower,
water closet, tub faucet, or associated pipes are leaking water. |
Level of Deficiency: |
- Level 1: You see a leak
or drip that is contained by the basin, and the faucet or pipe
can be used. |
- Level 2: N/A |
- Level 3: You see a
steady leak that is adversely affecting the area around it. |
-OR- |
The faucet or pipe cannot be used. |
Shower/Tub—Damaged/Missing (Bathroom—Unit) |
Deficiency: The shower, tub, or components
are damaged or missing. This includes associated hardware, such
as grab bars, shower doors, etc. |
Note: |
1. This does not include leaking faucets and pipes. |
2. If you see the stopper near the shower/tub area, do not
record it as a deficiency. |
Level of Deficiency: |
- Level 1: A stopper is
missing. |
- Level 2: The shower or
tub can be used, but you see cracks or extensive discoloration
in more than 50% of the basin. |
- Level 3: The shower or
tub cannot be used for any reason. The shower, tub, faucets,
drains, or associated hardware is missing or has failed. |
Ventilation/Exhaust System—Inoperable (Bathroom—Unit) |
Deficiency: The apparatus used to exhaust
air has failed. |
Note: |
1. If a resident has blocked an exhaust fan but it can function
properly, do not record this as a deficiency. |
2. If a resident has disconnected a fan, consider it functional
if it can be immediately reconnected for your inspection. |
3. If there was never a bathroom fan, do not record this as a
deficiency. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: An exhaust fan
is not functioning. |
-OR- |
A bathroom window cannot be opened. |
- Level 3: N/A |
|
There are many other bathroom
deficiencies - be sure to review and be aware of all of them, as
bathroom defects are some of the highest scoring in a Unit or Common
Area.
Bathroom cabinet damage includes damage to vanity and/or medicine.
Any damage what-so-ever is Level 1.
Leaks in Bathroom and well as Kitchen (two separate defects using
similar definitions) are Level 1 if all the leaking water goes down the
drain. They are Level 3 if the water goes anywhere else -
onto the floor, under the cabinet, etc.
A missing stopper in the tub is Level 1 like the sink issue.
Damage that renders any function of the tub or shower inoperable or
unsafe to use is Level 3.
An inoperable bath fan is Level 2 - but property staff may reconnect the
fan if it is unplugged, to demonstrate that it is operable with no
defect cited. |
|
|
|
|
Cabinets—Missing/Damaged (Kitchen—Unit) |
Deficiency: Cabinets are missing or the
laminate is separating. This includes cases, boxes, or pieces of
furniture with drawers, shelves, or doors, primarily used for
storage, mounted on walls or floors. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see that
10% to 50% of the cabinets, doors, or shelves are missing or the
laminate is separating. |
- Level 3: You see that
more than 50% of the cabinets, doors, or shelves are missing or
the laminate is separating. |
|
There is also a cabinets defect
for the Kitchen, but the definition is different from the Bathroom
Cabinets defect. |
|
|
It's the fashionable new "plywood look" complete with bar code stickers.
So, imagine that this door represents one
of nine cabinet doors in total.
1 divided by 9 = 0.111 or 11% of the doors.
This would be a Level 2 defect.
If 5 of 9 doors were damaged, missing, or delaminating, 5 divided by 9 =
0.555 or 56%, enough to cite this at Level 3
|
|
Dishwasher/Garbage Disposal—Inoperable (Kitchen—Unit) |
Deficiency: A dishwasher or garbage
disposal, if provided, does not function. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: The dishwasher
or garbage disposal does not function. |
- Level 3: N/A |
|
This definition covers two
different appliances - the disposal and the dishwasher - if any are
present.
There is only one defect whether one or both is inoperable |
|
|
Far more common than an
inoperable garbage disposal is an improperly wired disposal.
We have seen properties were every single disposal is improperly wired
due to replacements being done by unqualified persons or by unscrupulous
contractors cutting corners.
If the inoperable disposal was worth 0.2 points, the
exposed wires
hazard would be worth 1.6 points.
|
|
|
1.6 points times 20 units = 32.0 points.
Imagine losing 32 points on disposal wiring alone!
Disposal wiring issues can be found at the cable connector (top photo,)
at the junction box where wires come out of the wall or floor, or at the
junction box built into the disposal itself.
All wiring should have proper wire nuts and should be inside a junction
box with proper secured cover. There should be no gap that exposes
connections. |
|
Range Hood/Exhaust Fans—Excessive Grease/Inoperable
(Kitchen—Unit) |
Deficiency: The apparatus that draws out
cooking exhaust does not function. |
Level of Deficiency: |
- Level 1: An
accumulation of dirt, grease or other barrier noticeably reduces
the free passage of air. |
- Level 2: N/A |
- Level 3: The exhaust
fan does not function. |
-OR- |
You estimate that the flue may be completely blocked. |
|
The Bathroom and Kitchen each
have an Exhaust Fan issue, but the Bath fan can only be Level 2 while
the Kitchen fan can be Level 1 or Level 3 |
|
There is no specific defect in this photo |
If this exhaust does not
function at all it is Level 3
If the filter is dirty, it is Level 1
Until recently, a missing filter was NOT an exhaust fan issue, but many
inspectors would cite it as Sharp Edges. (We often appeal that
citation because the fan blades are not really sharp.)
As of mid 2016, REAC has instructed inspectors to cite as
missing filter as Level 3 ! ! |
|
|
There has been no comment from
REAC as to whether this new policy means that a filter that is in the
sink being washed makes the exhaust hood Level 3 or not.
One very disturbing
change in UPCS protocol - in our minds anyway - is that REAC is also
now instructing inspectors to cite Exterior Walls, Damaged, Level 3, if
the external cover of the kitchen or bathroom exhaust is damaged or
missing. |
|
Range/Stove—Missing/Damaged/Inoperable (Kitchen—Unit) |
Deficiency: The unit is missing or damaged. |
Note: Before the inspection starts, you should be given a list
of units under UFAS. Do not record these disconnected or
partially disconnected ranges/stoves as a deficiency. |
Level of Deficiency: |
- Level 1: The operation
of doors or drawers is impeded, but the stove is functioning. On
gas ranges, flames are not distributed equally. The pilot light
is out on 1 or more burners. |
- Level 2: One burner is
not functioning. |
- Level 3: The unit is
missing. |
-OR- |
Two or more burners are not functioning. |
-OR- |
The oven is not functioning. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
|
Properties with electric ranges
get lose far fewer points on stove issues than those with gas ranges.
So often, a little bit of dirt clogging a burner port will prevent it
from lighting.
|
|
|
We once knew a property manager
who told her residents that they "needed to make sure the top of their
stoves were clean" in the notification letter she sent out to announce
the inspection.
Many of the residents gave their stove a quick "wipe down" just as the
inspector knocked on their door - and the quick sloppy wide-down crammed
dirt into the burners. The property lost over 8 points that day,
just for burner not lighting!
Two of the burners on this stove will not light -
Level 3
(The top is just propped open,
nothing is missing)
|
|
Refrigerator—Missing/Damaged/Inoperable (Kitchen—Unit) |
Deficiency: The refrigerator is missing or
does not cool adequately for the safe storage of food. |
Level of Deficiency: |
- Level 1: The
refrigerator has an excessive accumulation of ice. |
-OR- |
The seals around the doors are deteriorated. |
- Level 2: N/A |
- Level 3: The
refrigerator is missing. |
-OR- |
The refrigerator does not cool adequately for the safe storage
of food. |
|
|
|
There is no specific defect in this photo |
The refrigerator is checked
for:
1 - It is present (not missing)
2 - It is cooling properly
3 - It is NOT iced up
4 - The gasket is not deteriorated
The refrigerator is NOT checked for:
Missing or broken handles, drawers, or shelves
Having been painted, dented, or otherwise cosmetic conditions
The scoring value of the refrigerator gasket is much lower than many
people assume.
This defect gets more attention than it deserves in our opinion. |
|
Sink—Missing/Damaged (Kitchen—Unit) |
Deficiency: A sink, faucet, or accessories
are missing, damaged or not functioning. |
Note: If a stopper is missing, do not record it as a deficiency. |
Level of Deficiency: |
- Level 1: You see
extensive discoloration or cracks in 50% or more of the basin,
but the sink and hardware can still be used to prepare food. |
- Level 2: N/A |
- Level 3: The sink or
hardware is either missing or not functioning. |
|
|
|
There is no specific defect in this photo |
The kitchen sink is checked for
operation of the faucets, operation of drain, condition of basin, and
for leaks.
Missing handle: L3
Inoperable hot or cold water: L3
Clogged drain (separate
defect)
Leaks (separate
defect)
inoperable sprayer is NOT a defect -
sprayers are only checked
for leaks
sink stopper not checked in kitchen |
|
Countertops—Missing/Damaged (Kitchen—Unit) |
Deficiency: A flat work surface in a kitchen
often integral to lower cabinet space is missing or
deteriorated. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: 20% or more of
the countertop working surface is missing, deteriorated, or
damaged below the laminate and is not a sanitary surface on
which to prepare food. |
- Level 3: N/A |
Plumbing—Clogged Drains (Kitchen—Unit) |
Deficiency: The water does not drain
adequately. |
Level of Deficiency: |
- Level 1: The basin does
not drain freely. |
- Level 2: N/A |
- Level 3: The drain is
completely clogged or has suffered extensive deterioration. |
Plumbing—Leaking Faucets/Pipes (Kitchen—Unit) |
Deficiency: You see that a basin faucet or
drain connections leak. |
Level of Deficiency: |
- Level 1: You see a leak
or drip that is contained by the basin or pipes, and the faucet
is functioning as it should. |
- Level 2: N/A |
- Level 3: You see a
steady leak that is having an adverse affect on the surrounding
area, and the faucet or pipe is not usable. |
|
More KITCHEN Defects:
The Counter Top definition is very lenient! There must be severe
damage (below the laminate) to 20% of the countertop before it is cited
for a defect.
Clogged drains works just like it does in the bathroom.
Leaks works just like it does in the bathroom.
A drippy faucet with water going down the drain is Level 1 |
|
|
|
|
Call-for-Aid—Inoperable (Unit) |
System to summon help. May be visual, audible, or both. May be
activated manually or automatically when pre-programmed
conditions are met. |
Deficiency: The system does not function. |
Note: Inspector should verify that the Call-for-Aid only alerts
local entities (on-site) prior to testing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The system
does not function. |
|
For some reason that we don't
understand, this is one of the most talked about topics when we do
a live seminar. Everybody gets upset that they are being cited for
a defect when the resident ties up the string or blocks it with
furniture.
Yes, it is a safety device, and Yes, we need to keep these working as
best we can.
However: |
|
|
You lose about one TENTH of a
point for this in a Unit. It is very rare that a property ever
loses an entire point on this defect for all Unit combined - you would
have to be cited for this in about ten Units to lose a whole point.
Yet, a single bad GFI in
one Unit is worth an entire point, and
these are often overlooked.
Setting good priorities for REAC preparations requires understanding the
comparative scoring values of the individual defects.
And, YES, this is a Level 3 defect as pictured. |
|
Laundry Area/Room—Dryer Vent Missing/Damaged/Inoperable (Unit) |
Place where soiled clothes and linens are washed and/or dried. |
Deficiency: Inadequate means is available to
vent accumulated heat/lint to the outside. The dryer vent is
missing, damaged or inoperable. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: Dryer vent is
missing, damaged or is visually determined to be inoperable
(blocked). Dryer exhaust is not effectively vented to the
outside. |
|
|
|
|
This is another Level 3 defect
that is worth about a tenth of a point in the typical Unit.
For a Common Area Laundry Room, when there is a single building, it can
be worth 3 or 4 points -
so check this!
It will count against your score even if the laundry equipment is
maintained by a third party like a vending company! |
|
Stairs (Unit) |
Series of 4 or more steps, or flights of steps, joined by
landings connecting levels of a unit. Includes supports, frame,
treads and handrails. |
This inspectable item can have the following deficiencies: |
Broken/Damaged/Missing Steps |
Broken/Missing Hand Railing |
Broken/Damaged/Missing Steps (Stairs—Unit) |
Deficiency: The horizontal tread or stair
surface is damaged or missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: A step is
broken or missing. |
Broken/Missing Hand Railing (Stairs—Unit) |
Deficiency: The handrail is damaged or
missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The handrail
for 4 or more stairs is either missing, damaged, loose or
otherwise unusable. |
|
The missing handrail defect
uses the same criteria as the similar Site defect - a handrail is
required if there are 4 or more steps.
Steps means risers.
When counting steps, we count the risers to avoid semantic confusion
between what is a "step" and what is a "landing." |
|
|
A stair
tread is partially collapsed.
This is a Level 3 defect.
If the rusty metal has a jagged edge, we
might also have a Sharp Edges hazard. |
|
Smoke Detector—Missing/Inoperable (Unit) |
Sensor to detect the presence of smoke and activate an alarm.
May be battery operated or hard-wired to electrical system. May
provide visual signal, audible signal or both. |
Deficiency: A smoke detector will not
activate or is missing. |
Note: |
1. There must be at least 1 smoke detector on each level. |
2. If 2 or more smoke detectors are on the same level in visible
proximity, at least 1 of the smoke detectors must function as it
should. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: A single smoke
detector is missing or does not function as it should. |
|
Yes - it's "Life Threatening"
Yes - as an "Exigent Health and Safety" issue, it requires immediate
repair within 24 hours
No - you do NOT lose any points for this defect. |
|
|
Level 3 |
|
Bulging/Buckling (Ceiling—Unit) |
Deficiency: The ceiling is bowed, deflected,
sagging, or is no longer aligned horizontally to the extent that
ceiling failure is possible. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or a problem with alignment. |
Comment: |
- Level 3: If you as an
inspector have concerns about the possibility of failure, inform
the property representative that an inspection by a professional
engineer is suggested. |
Compare to:
Bulging/Buckling (Floors—Unit) |
Deficiency: A floor is bowed, deflected,
sagging, or is no longer aligned horizontally. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or a lack of horizontal alignment. |
Comment: |
- Level 3: If you have
any doubt about the severity of this condition, request an
inspection by a structural engineer. |
Bulging/Buckling (Walls—Unit) |
Deficiency: A wall is bowed, deflected,
sagged or is no longer vertically aligned. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or that the wall is no longer
vertically aligned. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, request an
inspection by a structural engineer. |
|
The three separate Inspectable
Items:
- Ceilings
- Floors
- Walls
All have very similar defects.
All three of these structural surfaces can be cited for
Bulging/Buckling |
|
|
Here's an example for a Unit
ceiling...
It can only be Level 3 |
|
Peeling/Needs Paint (Walls—Unit) |
Deficiency: |
—Paint is peeling, cracking, flaking or otherwise deteriorated. |
-OR- |
—A surface is not painted. |
Note: Before the inspection starts, you should be given a list
of UFAS buildings/units. For the buildings/items on this list,
do not record as deficiencies any superficial surface/paint
damage caused by wheelchairs, walkers or medical devices. |
Level of Deficiency: |
- Level 1: The affected
area affected is more than 1 square foot but less than 4 square
feet. |
- Level 2: The affected
area is more than 4 square feet. |
- Level 3: N/A |
Compare to:
Peeling/Needs Paint (Ceiling—Unit) |
Deficiency: |
—You see paint that is peeling, cracking, flaking, or otherwise
deteriorated. |
-OR- |
—You see a surface that is not painted. |
Level of Deficiency: |
- Level 1: The affected
area is larger than 1 square foot, but smaller than 4 square
feet. |
- Level 2: The affected
area is larger than 4 square feet. |
- Level 3: N/A |
Peeling/Needs Paint (Floors—Unit) |
Deficiency: For floors that are painted, you
see paint that is peeling, cracking, flaking, or otherwise
deteriorated. |
Level of Deficiency: |
- Level 1: The area
affected is more than 1 square foot, but less than 4 square
feet. |
- Level 2: The area
affected is more than 4 square feet. |
- Level 3: N/A |
|
The three separate Inspectable
Items:
- Ceilings
- Floors
- Walls
All have very similar defects.
All three of these structural surfaces can be cited for
Peeling/Needs Paint |
|
If we go by the scoring value REAC places on paint in your Units,
the answer does not require one to paint for a REAC inspection |
On any of these surfaces, 1 to
4 square feet in need of paint is Level 1
More than 4 square feet is Level 2
Study the point values on these issues.
(Assuming 2 points per Unit)
A Level 2 paint on each of the 3 Inspectable Items would be worth
two one hundredths of one point.
Times 3 (ceiling, floor, wall) = 0.06
Times 20 units being inspected = 1.2 points - and that's at the greatest
extreme possible.
Realistically, maybe 50% of your Units get cited for paint on a ceiling
or wall. Let's say 10 times 0.02.
You would lose about 0.2 points on paint in your Units. |
|
Damaged (Walls—Unit) |
Deficiency: You see cracks and/or punctures
in the wall surface that may or may not penetrate completely.
Panels or tiles may be missing or damaged. |
Note: |
1. This does not include small holes created by hanging
pictures, etc. |
2. Control joints/construction joints should not be recorded as
a deficiency. |
3. Cracks that have been repaired or sealed properly should not
be considered a deficiency. |
Level of Deficiency: |
- Level 1: In a wall, you
find a hole, crack, missing tile or panel, or other damage that
is between 1 square inch and 8 1/2 inches by 11 inches. The hole
does not penetrate the adjoining room/area. You cannot see
through it to the adjoining area. |
-OR- |
You find a crack greater than 1/8 inch wide and at least 11
inches long. |
- Level 2: In a wall, you
find a hole, missing tile or panel, or other damage that is
larger than a sheet of paper, 8 1/2 inches by 11 inches, and
does not penetrate the adjoining room. You cannot see through it
to the adjoining area. |
- Level 3: You find a
hole of any size that penetrates an adjoining room. You can see
through the hole. |
-OR- |
Two or more walls have Level 2 holes. |
Comments: |
- Level 3: If a hole or
crack is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
If you as an inspector have concerns about the possibility of
failure, inform the property representative that an inspection
by a professional engineer is suggested. |
Compare to:
Holes/Missing Tiles/Panels/Cracks (Ceiling—Unit) |
Deficiency: |
- The ceiling surface has punctures that may or may not
penetrate completely. |
-OR- |
- Panels or tiles are missing or damaged. |
Level of Deficiency: |
- Level 1: You see small
holes that are no larger than a sheet of paper, 8 1/2 inches by
11 inches. |
-OR- |
No hole or crack penetrates the area above. |
-OR- |
You see that no more than 3 tiles or panels are missing. |
-OR- |
You see a crack more than 1/8 inch wide and 11 inches long. |
- Level 2: You see a hole
that is larger than a sheet of paper, 8 1/2 inches by 11 inches,
but it does not penetrate the area above. You cannot see through
it. |
-OR- |
You see that more than 3 tiles or panels are missing. |
-OR- |
You see a crack more than 1/8 inch wide and 11 inches long. |
- Level 3: You see a hole
that penetrates the area above. You can see through it. |
Comment: |
- Level 3: If a hole or
crack is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
|
The two separate Inspectable
Items:
- Ceilings
- Walls
Both a very similar defects for general damage like holes or cracks.
While the exact NAME of the defects is different, the definitions are
exactly the same for all practical purposes.
|
|
|
The
residents in this building figured out that, while the steel door was
pretty sturdy, it was much easier to get into this area through the
drywall materials which did not offer as much resistance as the door.
"You can se through it"
Level 3 |
|
Soft Floor Covering Missing/Damage (Floors—Unit) |
Deficiency: You see damaged and/or missing
soft floor covering. |
Level of Deficiency: |
- Level 1: You estimate
that only 5% to 10% of any single soft floor covering has
stains, surface burns, shallow cuts, small holes, tears, loose
areas, or exposed seams. The covering is fully functional, and
there is no safety hazard. |
- Level 2: You estimate
that 10% to 50% of any single soft floor covering has burn
marks, cuts, tears, holes, or large sections of exposed seams
that expose the underlying material. There is no safety hazard. |
- Level 3: You estimate
that more than 50% of any single soft floor covering is damaged. |
-OR- |
Damage to the soft floor covering exposes the underlying
material. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
|
|
|
|
If we consider that this is
staining that ruins the carpet, we could go out on a limb and say 100%
of the carpet in this room needs to be replaced, and we could call this
Level 3.
However, "dirty" and "stained" are different things.
It might be more reasonable to say that a little less than 10% of the
carpet in this area is actually damaged or permanently stained -
bringing this to a Level 1.
This is one of those cases were inspector judgment can make a very
significant difference in the REAC score. |
|
Hard Floor Covering Missing/Damaged Flooring/Tiles
(Floors—Unit) |
Deficiency: You see that hard flooring, terrazzo, hardwood,
ceramic tile, sheet vinyl, vinyl tiles, or other similar
flooring material, is missing section(s), is missing, or
presents a tripping or cutting hazard, associated with but not
limited to holes or delamination. |
Level of Deficiency: |
- Level 1: For any single
floor surface, you see deficiencies in areas of the floor
surface. You estimate that 5% to 10% of the floor is affected,
and there are no safety problems. |
- Level 2: You estimate
that 10% to 50% of any single floor surface is affected, but
there are no safety problems. |
- Level 3: You estimate
that more than 50% of any single floor surface is affected by
Level 1 deficiencies. |
-OR- |
The condition causes a safety problem. |
|
|
|
|
Broken or missing tiles are a
lot easier to quantify.
While it is hard to actually see and count the number of bad tiles in
the photo, let's say just over 10% are damaged or missing in this room.
That would put us at Level 2. |
|
Damaged/Deteriorated Trim
(Walls—Unit) |
Deficiency: Cove molding, chair rail, base
molding or other decorative trim is damaged or has decayed. |
Note: Before the inspection starts, you should be given a list
of UFAS buildings/units. For the buildings/units on this list,
do not record superficial surface/paint damage caused by
wheelchairs, walkers or medical devices as a deficiency. |
Level of Deficiency: |
- Level 1: You see small
areas of deterioration in the trim surfaces, and you estimate
that 5% to 10% of the wall area is affected. |
- Level 2: You see large
areas of deterioration in the trim surfaces, and you estimate
that 10% to 50% of the wall area is affected. |
- Level 3: You see
significant areas of deterioration in the wall surfaces, and you
estimate that more than 50% of the wall area is affected. |
|
|
|
|
Let's say about 50% of the wall
trim is missing. By definition, this would be Level 2 unless it
exceeds 50%, and then it would become Level 3. |
|
Also see below:
Mold/Mildew/Water Stains/Water Damage
(for Ceilings, Floors and Walls)
Rot/Deteriorating Subfloors
(for Floors)
|
|
|
Full definitions,
derived from Federal Register |
|
|
Unit Inspectable Items |
Items to inspect for “Unit” are as follows: |
Bathroom |
Call-for-Aid |
Ceiling |
Doors |
Electrical System |
Floors |
Hot Water Heater |
HVAC System |
Kitchen |
Laundry Area |
Lighting |
Outlets/Switches |
Patio/Porch/Balcony |
Smoke Detector |
Stairs |
Walls |
Windows |
Bathroom (Unit) |
A room equipped with a water closet or toilet, tub and/or
shower, sink, cabinet(s) and/or closet. This inspectable item
can have the following deficiencies: |
Bathroom Cabinets—Damaged/Missing |
Lavatory Sink—Damaged/Missing |
Plumbing—Clogged Drains |
Plumbing—Leaking Faucet/Pipes |
Shower/Tub—Damaged/Missing |
Ventilation/Exhaust System—Inoperable |
Water Closet/Toilet—Damaged/Clogged/Missing |
Bathroom Cabinets—Damaged/Missing (Bathroom—Unit) |
Deficiency: You see damaged or missing
cabinets, vanity tops, drawers, shelves, doors, medicine
cabinets, or vanities. |
Level of Deficiency: |
- Level 1: You see
damaged or missing cabinets, vanity tops, drawers, shelves,
doors, medicine cabinets or vanities that are not functioning as
they should for storage or their intended purpose. |
- Level 2: N/A |
- Level 3: N/A |
Lavatory Sink—Damaged/Missing (Bathroom—Unit) |
Deficiency: A basin (sink) is missing or
shows signs of deterioration or distress. |
Note: If you see the stopper near the sink area, do not record
it as a deficiency. |
Level of Deficiency: |
- Level 1: The sink can
be used, but you see either of these: |
—There are cracks or extensive discoloration in more than 50% of
the basin; |
-OR- |
- A stopper is missing. |
- Level 2: N/A |
- Level 3: The sink
cannot be used, because the sink or associated hardware is
missing or has failed. |
Plumbing—Clogged Drains (Bathroom—Unit) |
Deficiency: Water does not drain adequately
in the shower, tub, or basin (sink). |
Level of Deficiency: |
- Level 1: Water does
not drain freely, but the fixtures can be used. |
- Level 2: N/A |
- Level 3: The fixtures
are not usable, because the drain is completely clogged or shows
extensive deterioration. |
Plumbing—Leaking Faucet/Pipes (Bathroom—Unit) |
Deficiency: You see that a basin, shower,
water closet, tub faucet, or associated pipes are leaking water. |
Level of Deficiency: |
- Level 1: You see a
leak or drip that is contained by the basin, and the faucet or
pipe can be used. |
- Level 2: N/A |
- Level 3: You see a
steady leak that is adversely affecting the area around it. |
-OR- |
The faucet or pipe cannot be used. |
Shower/Tub—Damaged/Missing (Bathroom—Unit) |
Deficiency: The shower, tub, or components
are damaged or missing. This includes associated hardware, such
as grab bars, shower doors, etc. |
Note: |
1. This does not include leaking faucets and pipes. |
2. If you see the stopper near the shower/tub area, do not
record it as a deficiency. |
Level of Deficiency: |
- Level 1: A stopper is
missing. |
- Level 2: The shower or
tub can be used, but you see cracks or extensive discoloration
in more than 50% of the basin. |
- Level 3: The shower or
tub cannot be used for any reason. The shower, tub, faucets,
drains, or associated hardware is missing or has failed. |
Ventilation/Exhaust System—Inoperable (Bathroom—Unit) |
Deficiency: The apparatus used to exhaust
air has failed. |
Note: |
1. If a resident has blocked an exhaust fan but it can function
properly, do not record this as a deficiency. |
2. If a resident has disconnected a fan, consider it functional
if it can be immediately reconnected for your inspection. |
3. If there was never a bathroom fan, do not record this as a
deficiency. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: An exhaust
fan is not functioning. |
-OR- |
A bathroom window cannot be opened. |
- Level 3: N/A |
Water Closet/Toilet—Damaged/Clogged/Missing (Bathroom—Unit) |
Deficiency: A water closet/toilet is damaged
or missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: Fixture
elements, seat, flush handle, cover etc., are missing or
damaged. |
-OR- |
The toilet seat is cracked, or the hinge is broken. |
- Level 3: The bowl is
fractured or broken and cannot retain water. |
-OR- |
The water closet/toilet is missing. |
-OR- |
There is a hazardous condition. |
-OR- |
The water closet/toilet cannot be flushed, because of
obstruction or another defect. |
Call-for-Aid—Inoperable (Unit) |
System to summon help. May be visual, audible, or both. May be
activated manually or automatically when pre-programmed
conditions are met. |
Deficiency: The system does not function. |
Note: Inspector should verify that the Call-for-Aid only alerts
local entities (on-site) prior to testing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The system
does not function. |
Ceiling (Unit) |
The visible overhead structure lining the inside of a room or
area. |
This inspectable item can have the following deficiencies: |
Bulging/Buckling |
Holes/Missing Tiles/Panels/Cracks |
Peeling/Needs Paint |
Mold/Mildew/Water Stains/Water Damage |
Bulging/Buckling (Ceiling—Unit) |
Deficiency: The ceiling is bowed, deflected,
sagging, or is no longer aligned horizontally to the extent that
ceiling failure is possible. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or a problem with alignment. |
Comment: |
- Level 3: If you as an
inspector have concerns about the possibility of failure, inform
the property representative that an inspection by a professional
engineer is suggested. |
Holes/Missing Tiles/Panels/Cracks (Ceiling—Unit) |
Deficiency: |
- The ceiling surface has punctures that may or may not
penetrate completely. |
-OR- |
- Panels or tiles are missing or damaged. |
Level of Deficiency: |
- Level 1: You see small
holes that are no larger than a sheet of paper, 8 1/2 inches by
11 inches. |
-OR- |
No hole or crack penetrates the area above. |
-OR- |
You see that no more than 3 tiles or panels are missing. |
-OR- |
You see a crack more than 1/8 inch wide and 11 inches long. |
- Level 2: You see a
hole that is larger than a sheet of paper, 8 1/2 inches by 11
inches, but it does not penetrate the area above. You cannot see
through it. |
-OR- |
You see that more than 3 tiles or panels are missing. |
-OR- |
You see a crack more than 1/8 inch wide and 11 inches long. |
- Level 3: You see a
hole that penetrates the area above. You can see through it. |
Comment: |
- Level 3: If a hole or
crack is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Peeling/Needs Paint (Ceiling—Unit) |
Deficiency: |
—You see paint that is peeling, cracking, flaking, or otherwise
deteriorated. |
-OR- |
—You see a surface that is not painted. |
Level of Deficiency: |
- Level 1: The affected
area is larger than 1 square foot, but smaller than 4 square
feet. |
- Level 2: The affected
area is larger than 4 square feet. |
- Level 3: N/A |
Mold/Mildew/Water Stains/Water Damage (Ceiling—Unit) |
Deficiency: You see mold or mildew that may
have been caused by saturation or surface failure or evidence of
water infiltration or other moisture producing conditions. |
Level of Deficiency: |
- Level 1: On 1 ceiling,
you see evidence of mold or mildew, such as a darkened area,
over a large area (4 square inches to 1 square foot). You may or
may not see water. |
- Level 2: N/A |
- Level 3: On 1 ceiling,
you estimate that a very large area (more than 1 square foot) of
its surface has been substantially saturated or damaged by mold
or mildew. The ceiling surface may have failed. |
Doors - see separate section
Electrical - see separate section
Floors (Unit) |
The visible horizontal surface system within a room or area
underfoot; the horizontal division between 2 stories of a
structure. |
This inspectable item can have the following deficiencies: |
Bulging/Buckling |
Hard Floor Covering Missing/Damaged Flooring/Tiles |
Mold/Mildew/Water Stains/Water Damage |
Peeling/Needs Paint |
Rot/Deteriorated Subfloor |
Soft Floor Covering Damage |
Bulging/Buckling (Floors—Unit) |
Deficiency: A floor is bowed, deflected,
sagging, or is no longer aligned horizontally. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or a lack of horizontal alignment. |
Comment: |
- Level 3: If you have
any doubt about the severity of this condition, request an
inspection by a structural engineer. |
Hard Floor Covering Missing/Damaged Flooring/Tiles (Floors—Unit) |
Deficiency: You see that hard flooring, terrazzo, hardwood,
ceramic tile, sheet vinyl, vinyl tiles, or other similar
flooring material, is missing section(s), is missing, or
presents a tripping or cutting hazard, associated with but not
limited to holes or delamination. |
Level of Deficiency: |
- Level 1: For any
single floor surface, you see deficiencies in areas of the floor
surface. You estimate that 5% to 10% of the floor is affected,
and there are no safety problems. |
- Level 2: You estimate
that 10% to 50% of any single floor surface is affected, but
there are no safety problems. |
- Level 3: You estimate
that more than 50% of any single floor surface is affected by
Level 1 deficiencies. |
-OR- |
The condition causes a safety problem. |
Mold/Mildew/Water Stains/Water Damage (Floors—Unit) |
Deficiency: You see mold or mildew that may
have been caused by saturation or surface failure or evidence of
water infiltration or other moisture producing conditions. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: On 1 floor,
you see evidence of mold or mildew, such as a darkened area,
over a large area (4 square inches to 1 square foot). You may or
may not see water. |
- Level 3: On 1 floor,
you estimate that a very large area (more than 1 square foot) of
its surface has been substantially saturated or damaged by mold
or mildew. The floor surface may have failed. |
Peeling/Needs Paint (Floors—Unit) |
Deficiency: For floors that are painted, you
see paint that is peeling, cracking, flaking, or otherwise
deteriorated. |
Level of Deficiency: |
- Level 1: The area
affected is more than 1 square foot, but less than 4 square
feet. |
- Level 2: The area
affected is more than 4 square feet. |
- Level 3: N/A |
Rot/Deteriorated Subfloor (Floors—Unit) |
Deficiency: The subfloor has decayed or is
decaying. |
Note: |
1. If there is any doubt, apply weight to detect noticeable
deflection. |
2. This type of defect typically occurs in kitchens and
bathrooms. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see small
areas of rot or spongy flooring that is more than 1 square foot,
but less than 4 square feet. |
- Level 3: You see large
areas of rot, more than 4 square feet, and applying weight
causes noticeable deflection. |
Comment: |
- Level 3: If you as an
inspector have concerns about the health and safety, inform the
property representative that an inspection by a professional
engineer is suggested. |
Soft Floor Covering Missing/Damage (Floors—Unit) |
Deficiency: You see damaged and/or missing
soft floor covering. |
Level of Deficiency: |
- Level 1: You estimate
that only 5% to 10% of any single soft floor covering has
stains, surface burns, shallow cuts, small holes, tears, loose
areas, or exposed seams. The covering is fully functional, and
there is no safety hazard. |
- Level 2: You estimate
that 10% to 50% of any single soft floor covering has burn
marks, cuts, tears, holes, or large sections of exposed seams
that expose the underlying material. There is no safety hazard. |
- Level 3: You estimate
that more than 50% of any single soft floor covering is damaged. |
-OR- |
Damage to the soft floor covering exposes the underlying
material. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Hot Water Heater (Unit) |
This inspectable item can have the following deficiencies: |
General Rust/Corrosion |
Inoperable Unit/Components |
Leaking Valves/Tanks/Pipes |
Misaligned Chimney/Ventilation System |
Missing Pressure Relief Valve |
General Rust/Corrosion (Hot Water Heater—Unit) |
Deficiency: The equipment or associated
piping/ducting shows evidence of flaking, oxidation,
discoloration, pitting, or crevices. |
Level of Deficiency: |
- Level 1: You see
superficial surface rust. |
- Level 2: You see
significant formations of metal oxides, flaking, discoloration,
or a pit or crevice. |
- Level 3: Because of
this condition, the equipment or piping does not function. |
Inoperable Unit/Components (Hot Water Heater—Unit) |
Deficiency: Hot water supply is not
available, because the system or system components have
malfunctioned. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: After
running, water from the hot water taps is not warmer than room
temperature. |
Leaking Valves/Tanks/Pipes (Hot Water Heater—Unit) |
Deficiency: You see water leaking from any
hot water system component, including valve flanges, stems,
bodies, domestic hot water tank, or its piping. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see water
leaking. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Misaligned Chimney/Ventilation System (Hot Water Heater—Unit) |
Deficiency: The exhaust system on a gas
fired or oil fired unit is misaligned. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see any
misalignment of an exhaust system on a gas fired or oil fired
unit that may cause improper or dangerous venting of gases. |
Missing Pressure Relief Valve (Hot Water Heater—Unit) |
Deficiency: The pressure relief valve on the
unit water heating system is missing or does not extend to the
floor. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see that
the pressure relief valve on the unit water heating system is
either missing or does not extend to the floor. |
HVAC System (Unit) |
System to provide heating, cooling and ventilation to the unit.
This does not include building heating or cooling system
deficiencies such as boilers, chillers, circulating pumps,
distribution lines, fuel supply, etc., or occupant owned or
supplied heating sources. |
This inspectable item can have the following deficiencies: |
Convection/Radiant Heat System Covers Missing/Damaged |
General Rust/Corrosion |
Inoperable |
Misaligned Chimney/Ventilation System |
Noisy/Vibrating/Leaking |
Convection/Radiant Heat System Covers Missing/Damaged
(HVAC—Unit) |
Deficiency: A cover on the
convection/radiant heat system is missing or damaged, which
could cause a burn or related injury. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: At least 1
cover is missing or substantially damaged, allowing contact with
heating/surface elements or associated fans. |
Comment: |
- Level 3: When the
system is operational during an inspection and you see a Level 3
deficiency, a real-time hazard exists, you must record it
manually under “Hazards (Health and Safety).” |
General Rust/Corrosion (HVAC—Unit) |
Deficiency: You see a component of the
system with deterioration from oxidation or corrosion of system
parts. Deterioration is defined as rust and/or formations of
metal oxides, flaking, or discoloration, or a pit or crevice. |
Level of Deficiency: |
- Level 1: You see
deterioration from rust and corrosion on the HVAC units in the
dwelling unit. The system still provides enough heating or
cooling. |
- Level 2: N/A |
- Level 3: N/A |
Inoperable (HVAC—Unit) |
Deficiency: The heating, cooling, or
ventilation system does not function. |
Note: If the HVAC system does not operate because of seasonal
conditions, do not record this as a deficiency. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The HVAC
system does not function; it does not provide the heating or
cooling it should. The system does not respond when the controls
are engaged. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Misaligned Chimney/Ventilation System (HVAC—Unit) |
Deficiency: The exhaust system on either a
gas, oil fired, or coal unit is misaligned. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see any
misalignment of an exhaust system on a gas fired, oil fired or
coal unit that may cause improper or dangerous venting of gases. |
Noisy/Vibrating/Leaking (HVAC—Unit) |
Deficiency: The HVAC distribution
components, including fans, are the source of unusual
vibrations, leaks, or abnormal noise. Examples may include, but
are not limited to, screeching, squealing, banging, shaking,
etc. |
Level of Deficiency: |
- Level 1: The HVAC
system shows signs of abnormal vibrations, other noise, or leaks
when engaged. The system still provides enough heating or
cooling to maintain a minimum temperature range in the major
living areas. |
- Level 2: N/A |
- Level 3: N/A |
Kitchen (Unit) |
A place where food is cooked or prepared. The facilities and
equipment used in preparing and serving food. |
This inspectable item can have the following deficiencies: |
Cabinets—Missing/Damaged |
Countertops—Missing/Damaged |
Dishwasher/Garbage Disposal—Inoperable |
Plumbing—Clogged Drains |
Plumbing—Leaking Faucets/Pipes |
Range Hoods/Exhaust Fans—Excessive Grease/Inoperable |
Range/Stove—Missing/Damaged/Inoperable |
Refrigerator—Missing/Damaged/Inoperable |
Sink—Missing/Damaged |
Cabinets—Missing/Damaged (Kitchen—Unit) |
Deficiency: Cabinets are missing or the
laminate is separating. This includes cases, boxes, or pieces of
furniture with drawers, shelves, or doors, primarily used for
storage, mounted on walls or floors. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: You see that
10% to 50% of the cabinets, doors, or shelves are missing or the
laminate is separating. |
- Level 3: You see that
more than 50% of the cabinets, doors, or shelves are missing or
the laminate is separating. |
Countertops—Missing/Damaged (Kitchen—Unit) |
Deficiency: A flat work surface in a kitchen
often integral to lower cabinet space is missing or
deteriorated. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: 20% or more
of the countertop working surface is missing, deteriorated, or
damaged below the laminate and is not a sanitary surface on
which to prepare food. |
- Level 3: N/A |
Dishwasher/Garbage Disposal—Inoperable (Kitchen—Unit) |
Deficiency: A dishwasher or garbage
disposal, if provided, does not function. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: The
dishwasher or garbage disposal does not function. |
- Level 3: N/A |
Plumbing—Clogged Drains (Kitchen—Unit) |
Deficiency: The water does not drain
adequately. |
Level of Deficiency: |
- Level 1: The basin
does not drain freely. |
- Level 2: N/A |
- Level 3: The drain is
completely clogged or has suffered extensive deterioration. |
Plumbing—Leaking Faucets/Pipes (Kitchen—Unit) |
Deficiency: You see that a basin faucet or
drain connections leak. |
Level of Deficiency: |
- Level 1: You see a
leak or drip that is contained by the basin or pipes, and the
faucet is functioning as it should. |
- Level 2: N/A |
- Level 3: You see a
steady leak that is having an adverse affect on the surrounding
area, and the faucet or pipe is not usable. |
Range Hood/Exhaust Fans—Excessive Grease/Inoperable
(Kitchen—Unit) |
Deficiency: The apparatus that draws out
cooking exhaust does not function. |
Level of Deficiency: |
- Level 1: An
accumulation of dirt, grease or other barrier noticeably reduces
the free passage of air. |
- Level 2: N/A |
- Level 3: The exhaust
fan does not function. |
-OR- |
You estimate that the flue may be completely blocked. |
Range/Stove—Missing/Damaged/Inoperable (Kitchen—Unit) |
Deficiency: The unit is missing or damaged. |
Note: Before the inspection starts, you should be given a list
of units under UFAS. Do not record these disconnected or
partially disconnected ranges/stoves as a deficiency. |
Level of Deficiency: |
- Level 1: The operation
of doors or drawers is impeded, but the stove is functioning. On
gas ranges, flames are not distributed equally. The pilot light
is out on 1 or more burners. |
- Level 2: One burner is
not functioning. |
- Level 3: The unit is
missing. |
-OR- |
Two or more burners are not functioning. |
-OR- |
The oven is not functioning. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
Refrigerator—Missing/Damaged/Inoperable (Kitchen—Unit) |
Deficiency: The refrigerator is missing or
does not cool adequately for the safe storage of food. |
Level of Deficiency: |
- Level 1: The
refrigerator has an excessive accumulation of ice. |
-OR- |
The seals around the doors are deteriorated. |
- Level 2: N/A |
- Level 3: The
refrigerator is missing. |
-OR- |
The refrigerator does not cool adequately for the safe storage
of food. |
Sink—Missing/Damaged (Kitchen—Unit) |
Deficiency: A sink, faucet, or accessories
are missing, damaged or not functioning. |
Note: If a stopper is missing, do not record it as a deficiency. |
Level of Deficiency: |
- Level 1: You see
extensive discoloration or cracks in 50% or more of the basin,
but the sink and hardware can still be used to prepare food. |
- Level 2: N/A |
- Level 3: The sink or
hardware is either missing or not functioning. |
Laundry Area/Room—Dryer Vent Missing/Damaged/Inoperable (Unit) |
Place where soiled clothes and linens are washed and/or dried. |
Deficiency: Inadequate means is available to
vent accumulated heat/lint to the outside. The dryer vent is
missing, damaged or inoperable. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: Dryer vent is
missing, damaged or is visually determined to be inoperable
(blocked). Dryer exhaust is not effectively vented to the
outside. |
Lighting—Missing/Inoperable (Unit) |
System to provide illumination to a room or area. Includes
fixtures, lamps, and supporting accessories. |
Deficiency: A lighting fixture is missing or
does not function as it should. The malfunction may be in the
total system or components, excluding light bulbs. |
Level of Deficiency: |
- Level 1: In 1 room in
a unit, a permanent lighting fixture is missing or not
functioning, and no other switched light source is functioning
in the room. |
- Level 2: In 2 rooms, a
permanent lighting fixture is missing or not functioning, and no
other switched light source is functioning in the rooms. |
- Level 3: In more than
2 rooms, a permanent light fixture is missing or not
functioning, and no other switched light sources are functioning
in the rooms. |
Outlets/Switches (Unit) |
The receptacle connected to a power supply or method to control
the flow of electricity. Includes 2 and 3 prong outlets, ground
fault interrupters, pull cords, 2 and 3 pole switches and dimmer
switches. |
This inspectable item can have the following deficiencies: |
Missing |
Missing/Broken Cover Plates |
Missing (Outlets/Switches—Unit) |
Deficiency: An outlet, switch or both are
missing. |
Note: This does not apply to empty junction boxes that were not
intended to contain an outlet or switch. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: An outlet,
switch or both are missing. |
Comment: |
- Level 3: If this
condition is a health and safety concern, you must record it
manually under “Electrical Hazards (Health and Safety).” |
Missing/Broken Cover Plates (Outlets/Switches—Unit) |
Deficiency: The flush plate used to cover
the opening around a switch or outlet is damaged or missing. |
Level of Deficiency: |
- Level 1: An outlet or
switch has a broken cover plate over a junction box, but this
does not cause wires to be exposed. |
- Level 2: N/A |
- Level 3: A cover plate
is missing, which causes wires to be exposed. |
Patio/Porch/Balcony—Baluster/Side Railings Damaged (Unit) |
Adjoining patio, porch or balcony. |
Deficiency: A baluster or side railing on
the porch/patio/balcony is loose, damaged or does not function,
which limits the safe use of this area. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The baluster
or side rails enclosing this area are loose, damaged or missing,
limiting the safe use of this area. |
Smoke Detector—Missing/Inoperable (Unit) |
Sensor to detect the presence of smoke and activate an alarm.
May be battery operated or hard-wired to electrical system. May
provide visual signal, audible signal or both. |
Deficiency: A smoke detector will not
activate or is missing. |
Note: |
1. There must be at least 1 smoke detector on each level. |
2. If 2 or more smoke detectors are on the same level in visible
proximity, at least 1 of the smoke detectors must function as it
should. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: A single
smoke detector is missing or does not function as it should. |
Stairs (Unit) |
Series of 4 or more steps, or flights of steps, joined by
landings connecting levels of a unit. Includes supports, frame,
treads and handrails. |
This inspectable item can have the following deficiencies: |
Broken/Damaged/Missing Steps |
Broken/Missing Hand Railing |
Broken/Damaged/Missing Steps (Stairs—Unit) |
Deficiency: The horizontal tread or stair
surface is damaged or missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: A step is
broken or missing. |
Broken/Missing Hand Railing (Stairs—Unit) |
Deficiency: The handrail is damaged or
missing. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: The handrail
for 4 or more stairs is either missing, damaged, loose or
otherwise unusable. |
Walls (Unit) |
The enclosure of the units and rooms. Materials for construction
include concrete, masonry block, brick, wood, glass block,
plaster and sheet-rock. Surface finish materials include paint
and wall coverings. |
This inspectable item can have the following deficiencies: |
Bulging/Buckling |
Damaged |
Damaged/Deteriorated Trim |
Mold/Mildew/Water Stains/Water Damage |
Peeling/Needs Paint |
Bulging/Buckling (Walls—Unit) |
Deficiency: A wall is bowed, deflected,
sagged or is no longer vertically aligned. |
Level of Deficiency: |
- Level 1: N/A |
- Level 2: N/A |
- Level 3: You see
bulging, buckling, sagging, or that the wall is no longer
vertically aligned. |
Comment: |
- Level 3: If you have
any doubt about the severity of the condition, request an
inspection by a structural engineer. |
Damaged (Walls—Unit) |
Deficiency: You see cracks and/or punctures
in the wall surface that may or may not penetrate completely.
Panels or tiles may be missing or damaged. |
Note: |
1. This does not include small holes created by hanging
pictures, etc. |
2. Control joints/construction joints should not be recorded as
a deficiency. |
3. Cracks that have been repaired or sealed properly should not
be considered a deficiency. |
Level of Deficiency: |
- Level 1: In a wall,
you find a hole, crack, missing tile or panel, or other damage
that is between 1 square inch and 8 1/2 inches by 11 inches. The
hole does not penetrate the adjoining room/area. You cannot see
through it to the adjoining area. |
-OR- |
You find a crack greater than 1/8 inch wide and at least 11
inches long. |
- Level 2: In a wall,
you find a hole, missing tile or panel, or other damage that is
larger than a sheet of paper, 8 1/2 inches by 11 inches, and
does not penetrate the adjoining room. You cannot see through it
to the adjoining area. |
- Level 3: You find a
hole of any size that penetrates an adjoining room. You can see
through the hole. |
-OR- |
Two or more walls have Level 2 holes. |
Comments: |
- Level 3: If a hole or
crack is a health and safety concern, you must record it
manually under “Hazards (Health and Safety).” |
If you as an inspector have concerns about the possibility of
failure, inform the property representative that an inspection
by a professional engineer is suggested. |
Damaged/Deteriorated Trim (Walls—Unit) |
Deficiency: Cove molding, chair rail, base
molding or other decorative trim is damaged or has decayed. |
Note: Before the inspection starts, you should be given a list
of UFAS buildings/units. For the buildings/units on this list,
do not record superficial surface/paint damage caused by
wheelchairs, walkers or medical devices as a deficiency. |
Level of Deficiency: |
- Level 1: You see small
areas of deterioration in the trim surfaces, and you estimate
that 5% to 10% of the wall area is affected. |
- Level 2: You see large
areas of deterioration in the trim surfaces, and you estimate
that 10% to 50% of the wall area is affected. |
- Level 3: You see
significant areas of deterioration in the wall surfaces, and you
estimate that more than 50% of the wall area is affected. |
Mold/Mildew/Water Stains/Water Damage (Walls—Unit) |
Deficiency: You see mold or mildew that may
have been caused by saturation or surface failure or evidence of
water infiltration or other moisture producing conditions. |
Level of Deficiency: |
- Level 1: On 1 wall,
you see evidence of mold or mildew, such as a darkened area,
over a large area (4 square inches to 1 square foot). You may or
may not see water. |
- Level 2: N/A |
- Level 3: On 1 wall,
you estimate that a very large area (more than 1 square foot) of
its surface has been substantially saturated or damaged by mold,
or mildew. The wall surface may have failed. |
Peeling/Needs Paint (Walls—Unit) |
Deficiency: |
—Paint is peeling, cracking, flaking or otherwise deteriorated. |
-OR- |
—A surface is not painted. |
Note: Before the inspection starts, you should be given a list
of UFAS buildings/units. For the buildings/items on this list,
do not record as deficiencies any superficial surface/paint
damage caused by wheelchairs, walkers or medical devices. |
Level of Deficiency: |
- Level 1: The affected
area affected is more than 1 square foot but less than 4 square
feet. |
- Level 2: The affected
area is more than 4 square feet. |
- Level 3: N/A |
Windows - see separate section
|
|
|
|
|
|
Compilation Bulletin 4.0 v. 2, page 32 |
|
|
B. Bathroom
1. All sinks, showers, and tubs must be inspected by operating the hot
and cold water faucets or controls.
2. A missing or inoperable mechanical stopper (in either a tub or sink)
shall be recorded as a [Bathroom Items], [Bathroom], [Bathroom Sink or
Shower or Tub (Unit)], [A stopper is missing (only if there is no
stopper in the (visible area)].
3. Do not record a [Bathroom Items], [Bathroom], [Bathroom
Ventilation/Exhaust System]… deficiency for bathrooms constructed
without either an exhaust fan or a window.
4. When a roof exhaust fan that vents bathrooms in a high rise is
inoperable, record a [Building Systems], [Roof Exhaust System], [Floor
R], [Damaged to the point of being inoperable] or [Building Systems],
[Roof Exhaust System], [Floor R], [Missing…] deficiency as applicable,
for the roof exhaust fan. Inspectors must not record a deficiency for
each unit bathroom that the roof exhaust fan services.
C. Call-For-Aid
1. Call-for-aid, as installed, must serve its intended function. For
example, the bell sounds an alarm, the
light turns on, and/or off-site personnel are notified when the system
is activated.
2. When recording a ...[Tested - Call-for-Aid as installed does not
serve its intended function] deficiency a
comment must be provided (e.g. coiled-up, not fully extended, more than
“x” distance from the floor,
taped to the wall, etc.).
3. If the property has replaced the old Call-for-Aid system with a new
electronic neck or hand-held type of
system, the presence of any part of an inoperable system that remains
must be recorded as ...[Alerts
local entities (on-site)], [Unable to test system] with an appropriate
comment.
4. Call-for-Aid Systems will not be evaluated for deficiencies if all
pull stations have been removed from the
resident’s apartments and all that remains is the light fixture over the
unit’s door and/or the old enunciator
panel is still mounted on a wall in the lobby. If any part of the old
system remains inside the unit, then the
inspector must evaluate this situation as an inoperable Call-for-Aid
system.
D. Ceiling
1. Hole, paint, and water stains/water damage/mold/mildew defects are
cumulative when they appear on
any one ceiling surface (per room).
2. Smoke, grease or dirt on ceiling surfaces that can be washed off is
not considered deteriorated paint.
E. Doors (Refer to the “Doors” section on pages 18 and 19)
F. Electrical System (Refer to the “Electrical” section on pages 21 and
22)
G. Floors
1. Stains on soft flooring (e.g., carpeting) affecting 5% to 100% of the
total similar soft floor material in the unit should be recorded as
[Floors], [appropriate room location], [Carpet is Missing/Damaged], [5%
to less than 10% of any single floor] resulting in a Level 1 deficiency.
Non-water stains on soft flooring are only applicable to Level 1; not to
Level 2 or Level 3.
2. When determining floor damage severity, the total percentage is based
on total area of similar material floor covering.
3. Cracks on basement floors are to be recorded under [Building
Exterior], [Foundations], [Crack or Gap (applies to both walls and
floors)]...
H. HVAC System
1. When a cover is missing on a convection or radiant heat system
resulting in sharp edges a [HVAC System], [appropriate room location],
[Convection/Radiant Heat System Covers Missing or Damaged], [This
condition may result in a Health and Safety concern] deficiency must be
recorded. After selecting the "Finish" button for the deficiency a
[Health and Safety] screen will automatically appear and the inspector
should select [Sharp Edges - This could cause cutting...]. If a burn
hazard is also present, the inspector must record this hazard manually
in [Health and Safety], [appropriate room location], [Hazards], [Any
Other - This Does pose a risk of bodily injury].
2. Inspectors are required to inspect either the heat or the air
conditioning system, but not both. Inspect whichever is in season at the
time of the inspection and verify that the system is functioning as
intended.
I. Kitchen
1. When qualifying a Kitchen in a client room, the room must contain an
area to store, prepare, and cook food. If all three of those criterion
are not met then do not inspect the room as a kitchen. A microwave can
be substituted for a range/stove/oven to establish a kitchen; however it
should not be inspected and does not take the place of an inoperable
range/stove/oven.
2. Cabinet deficiencies are based on defects observed on individual
components (doors, drawers, or shelves) as a percentage of the same
component’s total for the entire cabinet system. For example in a
sample unit’s kitchen:
Damaged: One shelf Total Components: 12 shelves = 8% damaged = NOD
Damaged: Two doors Total Components: 20 doors = 10% damaged = Level 2
Damaged: Six drawers Total Components: 8 drawers = 75% damaged = Level
3
Inspectors should record [Kitchen Items], [Kitchen], [Kitchen Cabinets],
[Cabinets, door, shelves, or laminate damaged or missing], [More
than 50% of cabinets, doors, shelves, or laminate damaged or missing]
which results in a “Unit – Cabinets - Missing/Damaged (Kitchen) - Level
3” deficiency.
3. Delaminating is to be recorded as cabinet damage when applicable.
Surface chipping or finish deterioration is not a recordable defect.
4. An exhaust fan in a kitchen that has been intentionally blocked is a
[Kitchen Items], [Kitchen], [Range Hood/Exhaust Fans], [Exhaust fan does
not function]... deficiency, unless there is an operable window in the
kitchen.
5. Inspecting Stoves and Ranges:
a. Inspectors will no longer turn on or off any ranges/stoves/ovens. The
POA must turn all ranges/stoves and ovens on and off during the
inspection to allow the inspector to determine if the appliance
functions as intended and record any observed deficiencies. The
inspector must remain in close proximity from the time the POA turns the
range/stove/oven on until it is turned off. If the POA refuses to turn
it on and off, the inspector is to: (1) record a deficiency as [Kitchen
Items], [Kitchen], [Range/Stove/Oven], [Gas or Electric...], [Burner(s)
not functioning], [There are two or more burners that are not
functioning]... and inform the POA of the Level 3 deficiency, (2) write
“Property refused to turn on and off the range/stove/oven,” in the
comment section, (3) call the REAC TAC and report that the POA refused
to turn the range/stove/oven on and off and, (4) record the REAC TAC
number,
reason, and description in the inspection software. Prior to the
inspection remind the POA to check for and remove all items that may be
damaged from the top of burners and inside ovens before turning on the
appliance.
6. If a burner(s) on a gas stove is not functioning, the property
representative must be given an opportunity to check the pilot light(s)
and re-light it if it is out. If all burners are operable after
re-lighting the pilot, record a [Kitchen Items], [Kitchen],
[Range/Stove/Oven], [Gas Range/Stove/Oven], [A pilot light is out]
deficiency. If a burner(s) still does not function after re-lighting or
property representative chooses not to check or light the pilot, record
a deficiency for the inoperable burner(s).
7. When burners have been removed from the stove for cleaning or repair,
but can be located during the inspection and reinstalled into the
stovetop, the missing burners are not a deficiency. As with a gas stove,
after they have been reinstalled they must be turned on and checked to
determine if they are functioning.
8. When control knobs have been removed from the stove, and can be
located during the unit inspection and reinstalled on the stove, it is
not a deficiency. If the knobs cannot be located, but the range and
stove still functions properly, record the missing knobs as a [Kitchen
Items], [Kitchen], [Range/Stove/Oven], [Gas or Electric...], [A control
knob is missing...] deficiency, except in those cases where it is clear
that they have been removed to protect the safety of the resident (e.g.
Alzheimer’s patient).
J. Laundry Area
1. Leaking faucets on laundry tubs are not a recordable deficiency in
the UPCS software.
2. If an interior dryer vent filter box is properly filled with water
and attached to an electric dryer, do not record a deficiency. These
devices are not intended for use on gas dryers.
K. Lighting
1. Fixture/lamp globes or bowls are not considered part of the lighting
system. Do not record missing globes as a deficiency as long as the
light functions.
2. Inspectors are no longer required to inspect rooms designed with no
light switch for lighting related deficiencies. However, the inspector
is still required to inspect permanent light fixtures for proper
operation per the UPCS definition.
3. A closet is considered as a separate room for light fixture
assessments.
L. Outlets/Switches
1. Missing Outlets/Switches: The deficiency [Outlet/Switches],
[appropriate room location], [Switch is missing or Outlet is missing]…
applies only to outlets and switches that are completely missing
resulting in exposed electrical wires.
2. Damaged Outlets/Switches: Outlets and switches that are so damaged
that electrical connections are exposed must be evaluated under [Health
and Safety], [appropriate room location], [Electrical Hazards], [Exposed
bare wires], [The exposed bare wires are not capped…]. If the switch is
inoperable or damaged with no exposed connections, evaluate this under
[Unit], [Lighting]...
M. Patio/Porch/Balcony
1. Damage to a concrete slab porch or entry stoop must be recorded in
Site, Walkways/Steps, as applicable.
2. Record damage to balusters and side rails in Baluster/Side Railings.
All other deficiencies observed on unit patios, porches, and balconies
must be recorded in the associated unit in their respective area.
N. Smoke Detector
1. Smoke detectors within a unit must be operable and located on each
living level including the basement, which excludes a crawl space or
unfinished attic. If two or more smoke detectors are on the same level
in visible proximity and cannot be isolated from one another (such as
closing a door), at least one of the smoke detectors must function as it
should.
2. If a smoke detector is not located in the unit/client room in nursing
homes, group homes and assisted living facilities, it is not a defect.
However, if a smoke detector does exist within the client room it must
be inspected for correct operation unless it is an integral part of the
building’s fire alarm system and current inspection documentation is
provided. If the smoke detectors in these types of facilities are
installed only in the common areas such as hallways and offices, the
inspector will record “NOD” for [Unit], [Smoke Detector] and enter a
comment stating that smoke detectors are located in common areas only in
the Building Comments field located on the Building screen.
O. Walls
1. An inspector must evaluate [Damaged/Deteriorated Trim], [Trim is
Damaged or Decayed] on any one wall as a percentage of the total trim on
that one wall surface. Missing trim must also be included in the
calculation as it is considered a form of deterioration.
2. Smoke, grease, or dirt on wall surfaces that can be washed off is not
considered deteriorated paint.
P. Water Heater
1. The end of the pressure relief valve or its extension on a hot water
heating system must be no more than 18 inches from the floor or piped to
a designed system, otherwise it must be recorded as a deficiency.
2. Water Heater is never recorded as “NA” (with the exception of units
with no domestic water connections) regardless of whether or not the
tank is located within the unit. Record deficiencies for the hot water
system in either [Unit], Water Heater] or [Building Systems], [Domestic
Water], whichever is most appropriate.
3. A leaking hose bib that services a single unit will be recorded under
[Unit], [Water Heater]. When the hose bib services a single common area
or multiple units it will be evaluated as [Systems], [Domestic Water].
Q. Windows (Refer to “Windows” section on page 20)
|
|
|
|
|
|
|
|
|
UPCS GUIDANCE & PROTOCOL CLARIFICATIONS
Effective date: May 23, 2016 |
|
|
|
|
|
Unit:
• The shower head leaks when the water is turned on but does not leak
when the water is off. Is this a defect? Yes. It is a defect and shall
be recorded as a L1 if contained and a L3 if not contained.
• The showerhead is missing. Is this a defect or not? It is a defect for
missing hardware.
• If the mechanical sink stopper is inoperable is it a L1 – sink stopper
defect or a L3 – hardware defect? It is a L1 – sink stopper defect.
• Upon entering the bathroom, the inspector observed that the water is
turned off to the sink and/or toilet. Is this a defect? If the water
cutoff valve under a sink or behind the toilet is turned off, the
inspector can allow the property rep to turn on the valve to allow
proper testing of the sink or toilet.
Unit: HVAC-
• If the HVAC system has holes in it from the manufacturer, can this be
considered exposed wires? If the holes expose bare wires and/or bare
connections it is an electrical defect.
• What should the inspector do if the window air conditioner in a unit
is unplugged? The inspector shall allow the property representative to
plug it in and then test it for correct operation. (HVAC is seasonable)
Unit: Kitchen Items-
• The range hood exhaust fan is
missing the filter. Is it a defect? Yes,
it is a defect. (Inoperable –L3)
• Is aluminum foil in the oven or on the stove top a defect? No defect
• Is a pizza box, plastic bags, etc., stored in the oven a defect? Yes.
It is recorded as Hazards- Other.
• What should the inspector do if the stove in a unit is unplugged? The
inspector will allow the property representative to plug it in and then
inspect the stove for correct operation.
• How do we inspect kitchen
sink sprayers? The sink sprayer is only
evaluated for leaks. If it is not present; it is not a defect.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|